Database
Address

Variable Name

Description

1013

DNP Slave Binary Input Event count This value contains the total number of

binary input events that have occurred.

1014

DNP Slave Analog Input Event
count

This value contains the total number of
analog input events that have occurred.

1015

DNP Slave Float Input Event Count This value contains the total number of

float events that have occurred.

1016

DNP Slave Double Input Event
Count

This value contains the total number of
double events that have occurred.

1017

DNP Slave bad function code error
(Application Layer Error)

This value counts the number of times a
bad function code for a selected
object/variation is received by the slave
device.

1018

DNP Slave object unknown error
(Application Layer Error)

This value counts the number of times a
request for an unsupported object is
received by the slave device.

1019

DNP Slave out of range error
(Application Layer Error)

This value counts the number of times a
parameter in the qualifier, range or data
field is not valid or out of range.

1020

DNP Slave message overflow error
(Application Layer Error)

This value counts the number of times an
application response message from the
slave is too long to transmit.

1021

DNP Slave multi-frame message
from DNP Master error (Application
Layer Error)

This value counts the number of times
the slave receives a multi-frame
message from the master. The
application does not support multi-frame
master messages.

1022

Unsolicited Message Errors

This value counts the number of
unsuccessful unsolicited messages
transmitted by the slave unit.

1023 Cycle

Count

This value is incremented each program
scan.

1024

DNP Slave synchronization error
count (Physical Layer Error)

This value counts the number of times a
sync error occurs. The error occurs when
extra bytes are received before the start
bytes (0x05 and 0x64) are received.

1025

DNP Slave overrun error count
(Physical Layer Error)

This value counts the number of times
the overrun error occurs. This error
occurs when the mainline Data Link
Layer routine cannot read the data
received on the communication port
before it is overwritten.

1026

DNP Slave length error count
(Physical Layer Error)

This value counts the number of times an
invalid length byte is received. If the
length of the message does not match
the length value in the message, this
error occurs.

1027

DNP Slave bad CRC error (Data
Link Layer Error)

This value counts the number of times a
bad CRC value is received in a
message.

This manual is related to the following products: