Communication port cables – ProSoft Technology 5201-DFNT-DNPS User Manual
Page 44
ProLinx DNPS ♦ ProLinx Gateway
Reference
DNP 3.0 Slave
User Manual
Page 44 of 86
ProSoft Technology, Inc.
December 1, 2009
Specification Description
Ethernet Port
(Ethernet protocol gateways
only)
10Base-T half duplex RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as
specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000
[ARP] frames-per-second and less than or equal to 5 minutes
duration
Application Serial Port(s)
(Serial protocol gateways
only)
RS-232/422/485
RS-232 handshaking configurable
RS-422/485 DB-9 to Screw Terminal Adaptor
Note: The number of serial application ports depends on the module
type, and the combination of protocols.
Serial Port Isolation
2500V RMS port signal isolation per UL 1577
3000V DC min. isolation port to ground and port to logic
Shipped with Each Unit
Mini-DIN to DB-9M serial cables
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal Adaptor for each serial
application port (serial protocols only)
3.2
Communication Port Cables
This section contains information on the cable and pin assignments for the
ProLinx gateway's serial ports (RS-232/422/485). The ProLinx gateway will come
with one to five serial ports, depending on the configuration purchased. In all
cases, the protocol serial ports will have the same pinouts.
Example: The 5202-MNET-MCM4 gateway contains five serial communication ports; four
configurable protocol application ports and one Configuration/ Debug port.
The 5201-MNET-MCM gateway contains two serial communication ports; one configurable
protocol application port and one Configuration/Debug port.
Each physical serial port has an eight-pin Mini-DIN jack connector. A six-inch
Mini-DIN-8Male to DB-9Male adapter cable is provided for each serial port. The
DB-9M provides connections for RS-232, wired as Data Terminal Equipment
(DTE), RS-422 and RS-485. The diagrams in the following topics detail the pin
assignments for several possible electrical interface connections.
3.2.1 Serial Port Cable Connections: Config/Debug and Port 0
This section contains information on the cable and pin assignments for the
ProLinx Communication Gateway module application serial ports (RS-
232/422/485).
The module will come with one to five serial ports, depending on the
configuration purchased. In all cases, the protocol serial ports will have the same
pin-outs.