background image

Reference ProLinx

DNPS

♦ ProLinx Gateway

User Manual

DNP 3.0 Slave


ProSoft Technology, Inc.

Page 69 of 86

December 1, 2009

DNP V3.00
DEVICE PROFILE DOCUMENT

When reporting Event Data as a slave unit

Time-outs while waiting for:

Data Link Confirm

: Configurable at module start-up (1 to 65535 mSec)

Complete Application Fragment

: Configurable at module start-up

Application Confirm

: Configurable at module start-up (1 to 65535 mSec)

Complete Application Response

: None

Sends/Executes Control Operations:

WRITE Binary Outputs

: Never

SELECT/OPERATE :

Always

DIRECT OPERATE

: Always

DIRECT OPERATE-NO ACK

: Always


Count > 1

: Always (1 to 255)

Pulse On

: Always

Pulse Off

: Always

Latch On

: Always

Latch Off

: Always


Queue :

Never

Clear Queue

: Never

Reports Binary Input Change Events when no specific
variation requested:

Reports time-tagged Binary Input Change Events when no
specific variation requested:

Only time-tagged

Binary Input Change with Time

Sends Unsolicited Responses:

Sends Static Data in Unsolicited Responses:

This is configurable at module start-up. If the number of
events for the Binary or Analog Input Events is greater than
0, unsolicited responses are supported. Use the
Enable/Disable Unsolicited function code from the DNP
master for control.

Never

Default Counter Object/Variation:

Counters Roll Over at:

Object :

20

32 Bits

Variation :

5

Sends Multi-Fragment Responses: Yes