beautypg.com

Serial port specifications – ProSoft Technology 5201-DFNT-DNPS User Manual

Page 42

background image

ProLinx DNPS ♦ ProLinx Gateway

Reference

DNP 3.0 Slave

User Manual


Page 42 of 86

ProSoft Technology, Inc.

December 1, 2009

Type Specifications

DNP Slave

Node address

0 to 65534 (software selectable)

Status Data

Error codes, counters and port status available per configured
slave port

3.1.2 Serial Port Specifications

Type Specifications

Serial Ports

Serial Port Adapter Cables

One Mini DIN to DB-9M adapter cable included for
each configurable serial port

Config Port Connector/ Pinout

DB-9F connector / DTE pinout

Serial Port Isolation

2500V RMS port-to-port isolation per UL 1577.

3000V DC min. port to ground and port to logic
power isolation.

Serial Port Protection

RS-485/422 port interface lines TVS diode protected
at +/- 27V standoff voltage.

RS-232 port interface lines fault protected to +/- 36V
power on, +/- 40V power off.

Note: On all ProLinx gateways, data from the application port on the main board, serial Port 0, is
not buffered. Packets go directly to and from the serial chipset to the processor. This has the
potential to cause the serial communications to become erratic at baud rates above 38,400 baud.
ProLinx gateways with 4 serial ports have a separate serial interface board for serial Ports 1, 2,
and 3. These serial ports are buffered and can handle communications up to 115,200 baud.