Data link confirm tout, Data link max retry, App layer confirm tout – ProSoft Technology 5201-DFNT-DNPS User Manual
Page 21: Unsolicited response, Class 1 unsol resp min, Class 2 unsol resp min, Class 3 unsol resp min
Start Here
ProLinx DNPS ♦ ProLinx Gateway
User Manual
DNP 3.0 Slave
ProSoft Technology, Inc.
Page 21 of 86
December 1, 2009
Data Link Confirm Tout
1 to 65535 milliseconds
Time period to wait for Master Data Link confirmation of last frame sent. This
time is in milliseconds. This parameter is only used if the frame is sent with
confirmation requested.
Data Link Max Retry
0 to 255 retries
Maximum number of retries at the Data Link level to obtain a confirmation. If this
value is set to 0, retries are disabled at the data link level of the protocol. This
parameter is only used if the frame is sent with confirmation requested.
App Layer Confirm Tout
1 to 65535 milliseconds
Event data contained in the last response may be sent again if not confirmed
within the millisecond time period set. If application layer confirms are used with
data link confirms, ensure that the application layer confirm timeout is set long
enough.
Unsolicited Response
Y or N
Set if the slave unit will send unsolicited response messages. If set to N, the
slave will not send unsolicited responses. If set to Y, the slave will send
unsolicited responses.
Class 1 Unsol Resp Min
1 to 255 events
Minimum number of events in Class 1 required before an unsolicited response
will be generated.
Class 2 Unsol Resp Min
1 to 255 events
Minimum number of events in Class 2 required before an unsolicited response
will be generated.
Class 3 Unsol Resp Min
1 to 255 events
Minimum number of events in Class 3 required before an unsolicited response
will be generated.