ProSoft Technology PTQ-AFC User Manual

Page 78

background image

Quick Start

PTQ-AFC ♦ Modicon Quantum Platform

User Manual

Liquid and Gas Flow Computer for Hydrocarbon Products

Page 78 of 259

ProSoft Technology, Inc.

June 23, 2011

6.8 Modbus

Database

The module supports two individual Modbus slaves (Primary and Virtual) to
optimize the polling of data from the remote SCADA system, or from the
processor (through the backplane). Refer to the Modbus Dictionary dialog box in
AFC Manager for information about Modbus addressing.

6.8.1 AFC

Modbus

Address

Space

Addressable Modbus registers are divided into four banks as shown in the
following table.

MODBUS Address Space Allocation: Total Modbus Registers: 131,072

Primary Slave Banks
(131072 registers)

Virtual Slave Banks
(20,000 registers)

Holding Registers

Input Registers

Holding Registers

Input Registers

From: 0

From: 0

From: 0

From: 0

To: 65535

To: 65535

To: 9999

To: 9999

The first 100 registers of the virtual slave (registers 0 through 99) are predefined
to map to the first 100 registers of the primary slave. This mapping cannot be
changed. Also, the Virtual Slave Input Registers can be accessed as Virtual
Slave Holding Registers by adding 10000 to the Modbus register address; for
example, Input Register 2386 is the same as Holding Register 12386.

Accessing the Data
The AFC Manager provides an easy way to read and write data from both slaves
through the Modbus Master Interface.