6.12.3 Event Id Tag
This 32-bit field has the following structure:
Bits
N
Meaning
31
1
0 Special, 1 Datum Point (e.g. sealable parameter)
If this bit is clear, then bits 19-00 contain a value from the Special event
tag list below; if the bit is set, then bits 19-00 have the interpretation
given here.
30
1
PLC offline; timestamp may not be accurate
This bit may also be set for a Special event.
29
1 [reserved]
28 to 24
5
Meter number, or 0 for Site
This field may also be set for a Special event.
23 to 20
4
[Meter] Stream number or 0; [Site] 0
This field may also be set for a Special event.
19 to 16
4
Datum type:
Value
Mnemonic
Format
0
Ubyt
Unsigned byte
1
Usht
Unsigned short integer
2
[reserved]
3
Ulng
Unsigned long integer
4
Sbyt
Signed byte
5
Ssht
Signed short integer
6
[reserved]
7
Slng
Signed long integer
8
Bbyt
Bitmap (up to 8 bits)
9
Bsht
Bitmap (up to 16 bits)
10
Bm24
Bitmap (up to 24 bits)
11
Blng
Bitmap (up to 32 bits)
12
Bool
Boolean (value 0 or 1)
13
DiBy
Dibyte (both high and low)
14
B448
Bitfield nybble/nybble/byte
15
Flot
Floating point
15 to 12
4
[reserved]
11 to 08
4
Group code
This value is one of the "measurement configuration changed" bit
numbers.
07 to 04
4
Subgroup code
This value is the ordinal number (starting at 0) of the subgroup of
parameters in the specified group.
03 to 00
4
Subgroup item code
Since a parameter subgroup may contain more than one item, this value
identifies the particular item; items are numbered from 0.