ProSoft Technology PTQ-AFC User Manual
Page 161
![background image](https://www.manualsdir.com/files/866175/content/doc161.png)
PTQ-AFC ♦ Modicon Quantum Platform
Meter Proving
Liquid and Gas Flow Computer for Hydrocarbon Products
User Manual
ProSoft Technology, Inc.
Page 161 of 259
June 23, 2011
38
Master meter in calibration
The master meter has at least one process input in
calibration mode. Ensure that all process inputs are
live
before attempting to use the master meter for
proving.
39
Master meter not enabled
The master meter is not enabled.
51
Invalid prover parameter
For a traditional (non-master-meter) prover, the base
prover volume (register 65036) must be greater than
zero, and, if the prover is single-walled, the inside
diameter, wall thickness, and modulus of elasticity
(registers 65038, 65040, and 65042) must all be
greater than zero.
52
Invalid prover controls
Some undefined bits in the at-enable controls
(register 65306 bits 0 through 7) have been set.