beautypg.com

ProSoft Technology PTQ-AFC User Manual

Page 230

background image

Reference PTQ-AFC

♦ Modicon Quantum Platform

User Manual

Liquid and Gas Flow Computer for Hydrocarbon Products

Page 230 of 259

ProSoft Technology, Inc.

June 23, 2011

Each archive configuration word has the following bitmap structure:

Bit

Description

0

Period select, hourly

1

Archive upon period end

2

Archive upon event

3

Reserved

4

Reset resettable accumulator 1 upon period end

5

Reset resettable accumulator 2 upon period end

6

Reset resettable accumulator 3 upon period end

7

Reset resettable accumulator 4 upon period end

8

Reset resettable accumulator 1 upon event

9

Reset resettable accumulator 2 upon event

10

Reset resettable accumulator 3 upon event

11

Reset resettable accumulator 4 upon event

12

Reserved

13

Reserved

14

Reserved

15

Reserved

Note: Bit 0 must be set only for the hourly archives.

Changes made directly to the Modbus table in this manner are not automatically
made to your open AFC configuration. To incorporate these changes into your
configuration so that they may be saved in the AFC file on your hard disk, you
must read back the meter configuration from the module after making the change
by using the "Read Configuration" button on the Meter Configuration window.

This manual is related to the following products: