ProSoft Technology PTQ-AFC User Manual
Page 166
Meter Proving
PTQ-AFC ♦ Modicon Quantum Platform
User Manual
Liquid and Gas Flow Computer for Hydrocarbon Products
Page 166 of 259
ProSoft Technology, Inc.
June 23, 2011
8.4.2 Meter Previous Prove Summary
This area contains summary data for the previous prove of each of the AFC’s
meter runs. Each time a new prove is enabled and before the Prove Results
area is reset, summary prove information for the meter previously proved (if any)
is copied to the meter’s Previous Prove Summary block, overwriting the old
information. This area supplies a small amount of the information presented in
the proving report.
The Previous Prove Summary block for each meter occupies 50 registers. Meter
#1’s block begins at input register 61600, so that Meter #2’s block is at 61650,
and so on; registers 61600 to 62399 are allocated to the Previous Prove
Summary blocks for up to 16 meter runs.