beautypg.com

ProSoft Technology MVI56E-MNETC User Manual

Page 83

background image

MVI56E-MNETC ♦ ControlLogix Platform

Ladder Logic

Modbus TCP/IP Client Enhanced Communication Module

User Manual

ProSoft Technology, Inc.

Page 83 of 183

February 3, 2013

MNETC.DATA.ReadData
The ReadData

controller tag array

size should be equal to or greater than the

value entered in the Read Register Count (page 44) parameter of the
configuration. For ease of use, this array should be dimensioned as a multiple of
200 words. This data is paged up to 200 words at a time from the module to the
processor. The

ladder logic places the data received into the proper position in

the ReadData array. This data is used for status and control in the processor

ladder logic.

The ReadData array is related to the contents of the Read Data area of the
module's internal database. To view the actual registers in the module's internal
database, access the database display from ProSoft Configuration Builder's
Diagnostics
menu. For more information, see the section on PCB Diagnostics
(page 95).