Mnet client x – ProSoft Technology MVI56E-MNETC User Manual
Page 48

Guide to the MVI56E-MNETC User Manual
MVI56E-MNETC ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Client Enhanced Communication Module
Page 48 of 183
ProSoft Technology, Inc.
February 3, 2013
Bit Input Offset
0 to 9999
This parameter defines the start register for Modbus command data in the
internal database. This parameter is enabled when a value greater than 0 is set.
For example, if the Bit Input Offset value is set to 3000, data requests for Modbus
Input Register address 10001 will use the internal database register 3000, bit 0. If
the Bit Input Offset is set to 3000, data requests for Modbus Coil register address
10016 will use the internal database register 3000, bit 15. Function code 2 is
affected.
Holding Register Offset
0 to 9999
This parameter defines the start register for the Modbus Command data in the
internal database. This parameter is enabled when a value greater than 0 is set.
For example, if the Holding Register Offset value is set to 4000, data requests for
Modbus Word register 40001 will use the internal database register 4000.
Function codes affected are 3, 6, 16, & 23.
Word Input Offset
0 to 9999
This parameter defines the start register for Modbus Command data in the
internal database. This parameter is enabled when a value greater than 0 is set.
For example, if the Word Input Offset value is set to 4000, data requests for
Modbus Word register address 30001 will use the internal database register
4000. Function code 4 is affected.
Connection Timeout
0 to 1200 seconds
This is the number of seconds the server will wait to receive new data. If the
server does not receive any new data during this time, it will close the
connection.
2.2.6 MNET Client x
This section defines general configuration for the MNET Client (Master).