MVI56E-MNETC ♦ ControlLogix Platform

Start Here

Modbus TCP/IP Client Enhanced Communication Module

User Manual

ProSoft Technology, Inc.

Page 33 of 183

February 3, 2013

3 Save and download the configuration to the module (page 65) and reboot.

Make sure that the ReadData

and WriteData

arrays do not overlap in the module

memory. For example, if your application requires 2000 words of WriteData
starting at register 0, then your Read Register Start

parameter must be set to a

value of 2000 or greater.