Using cipconnect to connect to the module – ProSoft Technology MVI56E-MNETC User Manual

Page 66

background image

Guide to the MVI56E-MNETC User Manual

MVI56E-MNETC ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Client Enhanced Communication Module

Page 66 of 183

ProSoft Technology, Inc.

February 3, 2013

2 In the Download

dialog box, click B

ROWSE

D

EVICE

(

S

) to open ProSoft

Discovery Service.

3 Select the module, and then click the right mouse button to open a shortcut

menu. On the shortcut menu, choose S

ELECT FOR

PCB.

4 Close ProSoft Discovery Service.
5 Click D

OWNLOAD

to transfer the configuration to the module.

2.4.1 Using CIPconnect to Connect to the Module

You can use CIPconnect

®

to connect a PC to the MVI56E-MNETC module over

Ethernet using Rockwell Automation’s 1756-ENBT EtherNet/IP

®

module. This

allows you to configure the MVI56E-MNETC module and network, upload and
download files, and view network and module diagnostics from a PC. RSLinx is
not required when you use CIPconnect. All you need are:
 The IP addresses and slot numbers of any 1756-ENBT modules in the path
 The ControlNet node numbers and slot numbers of any 1756-CNBx

ControlNet Bridge modules in the path

 The slot number of the MVI56E-MNETC in the destination ControlLogix

chassis (the last ENBT/CNBx and chassis in the path).

To use CIPconnect, follow these steps.