Backplane data transfer – ProSoft Technology MVI56E-MNETC User Manual
Page 112

Guide to the MVI56E-MNETC User Manual
MVI56E-MNETC ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Client Enhanced Communication Module
Page 112 of 183
ProSoft Technology, Inc.
February 3, 2013
5.2
Backplane Data Transfer
The MVI56E-MNETC module communicates directly over the ControlLogix
backplane. Data is paged between the module and the ControlLogix processor
across the backplane using the module's input and output images. The update
frequency of the images is determined by the scheduled scan rate defined by the
user for the module and the communication load on the module. Typical update
times range from 1 to 10 milliseconds.
This bi-directional transfer of data is accomplished by the module putting data in
the input image to send to the processor. Data in the input image is placed in the
processor's controller tags by ladder logic. The input image is set to 250 words.
Processor logic inserts data to the output image to be transferred to the module.
The module's firmware program extracts the data and places it in the module's
internal database. The output image is set to 248 words.
The following illustration shows the data transfer method used to move data
between the ControlLogix processor, the MVI56E-MNETC module and the
Modbus TCP/IP Network.