ProSoft Technology MVI56E-MNETC User Manual
Page 170

Guide to the MVI56E-MNETC User Manual
MVI56E-MNETC ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Client Enhanced Communication Module
Page 170 of 183
ProSoft Technology, Inc.
February 3, 2013
This action opens the Select Module dialog box. Enter generic in the text box
and select the G
ENERIC
1756
M
ODULE
. If you're using an earlier version of
RSLogix, expand O
THER
in the Select Module dialog box, and then select the
G
ENERIC
1756
M
ODULE
.
2 Click C
REATE
. This action opens the New Module dialog box.
3 Enter the Name, Description and Slot options for your application. You must
select the Comm Format as D
ATA
-
INT in the dialog box, otherwise the
module will not communicate. Click OK to continue.
Parameter
Value
Name
Enter a module identification string. Example: MNETC_2
Description
Enter a description for the module. Example: M
ODBUS
TCP/IP
C
LIENT
E
NHANCED
C
OMMUNICATION
M
ODULE
Comm Format
Select D
ATA
-INT.
Slot
Enter the slot number in the rack where the MVI56E-
MNETC module is located.
Input Assembly Instance
1
Input Size
250
Output Assembly Instance
2
Output Size
248
Configuration Assembly Instance
4
Configuration Size
0