Using the optional add-on instruction rung import, Before you begin, Overview – ProSoft Technology MVI56E-MNETC User Manual
Page 158
Guide to the MVI56E-MNETC User Manual
MVI56E-MNETC ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Client Enhanced Communication Module
Page 158 of 183
ProSoft Technology, Inc.
February 3, 2013
5.6
Using the Optional Add-On Instruction Rung Import
5.6.1 Before You Begin
Make sure that you have installed RSLogix 5000 version 16 (or later).
Download the Optional Add-On file
MVI56EMNETC_Optional_AddOn_Rung_v1_0.L5X from
www.prosoft-technology.com or copy it from the ProSoft Solutions CD-ROM.
Save a copy in a folder in your PC.
5.6.2 Overview
The Optional Add-On Instruction Rung Import contains optional logic for MVI56E-
MNETC applications to perform the following tasks.
Read/Write Ethernet Configuration
Allows the processor to read or write the module IP address, netmask and
gateway values.
Note: This is an optional feature. You can perform the same task through PCB
(ProSoft Configuration Builder). Even if your PC is in a different network group
you can still access the module through PCB by setting a temporary IP address.
Read/Write Module Clock Value
Allows the processor to read and write the module clock settings. The module
clock stores the last time that the Ethernet configuration was changed. The
date and time of the last Ethernet configuration change is displayed in the
scrolling LED during module power up.
Important: The Optional Add-On Instruction only supports the two features listed
above. You must use the sample ladder logic for all other features including
backplane transfer of Modbus TCP/IP data.