4.3.1 Status Data Definition
This section contains a description of the controller tags in the MNETC.STATUS
controller tag structure, which contains module and Client status data.
The first ten controller tags contain status data routinely transferred from the
module to the processor in the normal data transfer block sequence (page
114).
The next controller tags are used to request and receive Client status data via
the Client Status block functionality (page 122).
The next controller tags are the Event Sequence tags (blocks 4000 4100, and
4200), described on pages Error! Bookmark not defined. through Error!
Bookmark not defined..
The remaining controller tags are used to request and receive server status
data via the Server Status block functionality (page 123).
Note: In order to access up-to-date status data from these remaining controller
tags, you must ensure that a Client Status block or Server Status block was
recently received from the module. Client Status blocks and Server Status blocks
are not routinely sent from the module; they are returned on a once-per-request
basis as a response to a Client Status block request or Server Status block
request from the processor.
Note: To use the server capabilities, your MVI56E-MNETC module needs to have firmware version
3.01 or higher, and your MVI56E-MNETC Add-On Instruction needs to be version 1.8 or higher.
Earlier versions do not support server capabilities.