4 Select the Requested Packet Interval value for scanning the I/O on the

module. This value represents the minimum frequency that the module will
handle scheduled events. This value should not be set to less than 1
millisecond. The default value is 5 milliseconds. Values between 1 and 10
milliseconds should work with most applications.

5 Save the module. Click OK

to dismiss the dialog box. The Controller

Organization window now displays the module's presence.

6 Copy the User-Defined Data Types from the sample program into your

existing RSLogix 5000 project.

7 Copy the Controller Tags from the sample program into your project.

8 Copy the Ladder Rungs from the sample program into your project.