5.1
Product Specifications
The MVI56E Modbus TCP/IP Client Enhanced Communication Module allows
Rockwell Automation
®
ControlLogix
®
Programmable Automation Controllers
(PACs) to interface easily with Modicon Programmable Automation Controller
(PACs) , as well as multiple Modbus TCP/IP server-compatible instruments and
devices. The multi-Client module improves performance when controlling multiple
servers on a Modbus TCP/IP network, by supporting up to 30 Clients. It also
supports up to 20 server connections (10 MNET, 10 MBAP).
MVI56E enhancements include configuration and management through the
module’s Ethernet port, and CIPconnect
®
technology for bridging though
ControlNet™ and EtherNet/IP™ networks.
5.1.1 General Specifications
Backward compatible with previous MVI56-MNETC versions
Single-slot 1756 ControlLogix backplane compatible
10/100 Mbps auto crossover detection Ethernet configuration and application
port
User-definable module data memory mapping of up to 10,000 16-bit registers
CIPconnect-enabled network configuration and diagnostics monitoring using
ControlLogix 1756-ENxT and 1756-CNB modules and EtherNet/IP pass-
through communication
ProSoft Configuration Builder (PCB) software supported, a Windows-based
graphical user interface providing simple product and network configuration
Sample ladder logic and Add-On Instructions (AOI) are used for data transfer
between module and processor
4-character, alpha-numeric, scrolling LED display of status and diagnostics
data in plain English
– no cryptic error or alarm codes to decipher
ProSoft Discovery Service (PDS) software used to locate the module on the
network and assign temporary IP address
Personality Module - a non-volatile industrial-grade Compact Flash (CF) card
used to store network and module configuration for easy disaster recovery,
allowing quick in-the-field product replacement by transferring the CF card
5.1.2 Modbus TCP/IP Specifications
ProSoft Technology’s Modbus TCP/IP implementation (MNET) includes both
Client (Master) and server (slave) capabilities.
Modbus TCP/IP Server (Slave)
Supports ten independent server connections for Service Port 502 (MBAP)
Supports ten independent server connections for Service Port 2000
(Encapsulated)
Accepts Modbus Function Codes 1, 2, 3, 4, 5, 6, 7, 8, 15, 16, 17, 22 and 23
Module data can be derived from other Modbus server devices on the
network through the Client or from the ControlLogix processor