Guide to the MVI56E-MNETC User Manual

MVI56E-MNETC ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Client Enhanced Communication Module

Page 22 of 183

ProSoft Technology, Inc.

February 3, 2013

3 In the New Module dialog box, enter the following values.

Parameter

Value

Name

Enter a module identification string. Example: MNETC

Description

Enter a description for the module. Example: M

ODBUS

TCP/IP

C

LIENT

E

NHANCED

C

OMMUNICATION

M

ODULE

Comm Format

Select D

ATA

-INT.

Slot

Enter the slot number in the rack where the MVI56E-MNETC
module is located.

Input Assembly Instance

1

Input Size

250

Output Assembly Instance

2

Output Size

248

Configuration Assembly Instance

4

Configuration Size

0

Important: You must select the Comm Format as D

ATA

-

INT in the dialog box;

otherwise the module will not communicate over the backplane of the
ControlLogix rack.

4 Click OK

to continue.

5 Edit the Module Properties. Select the Requested Packet Interval value for

scanning the I/O on the module. This value represents the minimum
frequency at which the module will handle scheduled events. This value
should not be set to less than 1 millisecond. The default value is 5
milliseconds. Values between 1 and 10 milliseconds should work with most
applications.

6 Save the module.