ProSoft Technology MVI56-101S User Manual
Page 98

Reference MVI56-101S
♦ ControlLogix Platform
User Manual
IEC 60870-5-101 Slave Communication Module
Page 98 of 193
ProSoft Technology, Inc.
August 2, 2011
5.1.3 Functional
Specifications
The MVI56-101S module accepts commands from an attached master unit. A
port configured as a virtual slave permits a remote master to interact with all data
contained in the module. This data can be derived from the ControlLogix
processor. The remote master device uses the fully-configured databases in the
module to control outputs and monitor inputs. The module can operate in
balanced or unbalanced mode.
Supports time stamp events
Supports time and data synchronization from a master or the processor
Supports monitored data
Event queue supports 99 points for each data type
Reports events by configurable priority order
Order monitored points by interrogation groups
Configurable deadband for monitored measured points
Supports Master Class 1 and Class 2 polls with configurable parameters
Acknowledgement transmission is handled internally by the module
Configurable data link address, Common ASDU address and Information
Object Address
Configurable pulse duration