ProSoft Technology MVI56-101S User Manual
Page 105
MVI56-101S ♦ ControlLogix Platform
Reference
IEC 60870-5-101 Slave Communication Module
User Manual
ProSoft Technology, Inc.
Page 105 of 193
August 2, 2011
Get Module Time Block (9970)
Block 9970 identification code requests the module’s date and time. Use this
data to set the ControlLogix processor clock.
Block Format for Write
Word Offset in Block
Data Field(s)
Description
0 Block
ID
This field contains the value of 9970 identifying the
block type to the module.
1 to 247
Not Used
Not Used
The module responds to a valid block 9970 request with a block containing the
requested date and time. The format of this block is shown in the following table.
Block Format for Read
Word Offset in Block
Data Field(s)
Description
0 Reserved
Reserved
(0)
1
Block Write ID This is the next block requested by the module.
2 Year
This field contains the four-digit year for the new time
value.
3 Month
This field contains the month value for the new time.
Valid entries for this field are in the range of 1 to 12.
4 Day
This field contains the day value for the new time. Valid
entries for this field are in the range of 1 to 31.
5 Hour
This field contains the hour value for the new time. Valid
entries for this field are in the range of 0 to 23.
6 Minute
This field contains the minute value for the new time.
Valid entries for this field are in the range of 0 to 59.
7 Seconds
This field contains the second value for the new time.
Valid entries for this field are in the range of 0 to 59.
8 Milliseconds
This field contains the millisecond value for the new
time. Valid entries for this field are in the range of 0 to
999.
9 to 248
Not Used
Not Used
249
Block Read ID This field contains the block identification code of 9970
for the block.