2.16 [C_BO_NA_1]
This section defines the Command 32-bit Bitstring Point database. This
information is sourced from the remote Master and is transferred to the database.
You can associate a command with a Monitored Double-Point database value to
coordinate the command/monitor operation. You must enter the correct Monitor
Point # and Monitor DB Address values in the table. If the Require Select
parameter is not set to zero, a select command must be received before an
execute command will be processed.
This section takes the following parameters:
Point
#
DB
Address
Monitor Point #
Monitor
DB
Address
Each point is four 8-bit bytes and the DB Address value corresponds to the
double word offset in the module memory database.
The DB address should be located in a database area that is being constantly
moved from the Master to the module.
For additional information on how to set these parameters, see the Reference
chapter of this manual.