ProSoft Technology MVI56-101S User Manual
Page 130
Reference MVI56-101S
♦ ControlLogix Platform
User Manual
IEC 60870-5-101 Slave Communication Module
Page 130 of 193
ProSoft Technology, Inc.
August 2, 2011
5.3.5 Using
Control
(Command) Information Objects
The MVI56-101S module supports the following Control information objects:
ASDU Type
Information Object Description
C_SC_NA Control
Single
Command
C_DC_NA
Control Double Command
C_RC_NA
Control Regulating Step Command
C_BO_NA
Control 32-Bit Bitstring Command
C_SE_NA
Control Normalized Value Set Point Command
C_SE_NB Control
Scaled
Value Set Point Command
C_SE_NC
Control Short Floating-Point Value Set Point Command
Each Control information object is identified by its Information Object Address.
For each Control information object, configure the following parameters:
Point # - This is the Information Object Address of the information object. It
identifies the information object in the network. This address must be unique for
each Common ASDU Address in the network.
DB Address - This is the database location in the MVI56-101S module
associated with the information object.
Monitor Point # - This is the Information Object Address of the associated
Monitor information object to be sent to the Client once the Control request is
received.
Monitor DB Address - The user might (optionally) configure a Monitor information
object to be sent by the MVI56-101S module when it receives the command for
that specific information object.
Require Select - This parameter configures the information object to require a
Select request before the Operate command.
Example (C_SC_NA)