ProSoft Technology MVI56-101S User Manual
Page 57
MVI56-101S ♦ ControlLogix Platform
Configuring the MVI56-101S Module
IEC 60870-5-101 Slave Communication Module
User Manual
ProSoft Technology, Inc.
Page 57 of 193
August 2, 2011
2.8 [M_BO_NA_1]
This section defines the Monitored 32-bit Bitstring Data Point database. This
information is sourced from the database and is transferred to the remote Master
unit.
This section takes the following parameters:
Point
#
DB
Address
Groups
IV DB Bit
Each point is four 8-bit bytes (two 16-bit words) and the DB Address value
corresponds to the double word offset in the module memory database.
The DB address should be located in a database area that is being constantly
moved from the module to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.