MVI56-101S Error Status Table
This section contains a listing of the MVI56-101S module's status data area. This
file is located at the MVI56-101S database starting at address 4000. You may
also configure an additional area using the "Error Offset" parameter.
Offset Parameter Description
4000 Scan
Count
This status value contains a counter incremented on each
scan of the module's main loop.
4001 to 4002 Product Name
This two-word data area contains the text values representing
the product name.
4003 to 4004 Revision
This two-word data area contains the text values for the
revision number.
4005 to 4006 Op Sys #
This two-word data area contains the text values for the
operating system number.
4007 to 4008 Run Number
This two-word data area contains the text values for the run
number.
4009
Read Blk Cnt
This word contains the total number of block read operations
successfully executed.
4010
Write Blk Cnt
This word contains the total number of block write operations
successfully executed.
4011
Parse Blk Cnt
This word contains the total number of write blocks
successfully parsed.
4012
Error Blk Cnt
This word contains the total number of block transfer errors.
4013 Port
Selected
This parameter determines which port on the module is being
utilized. If the value is set to 0, the primary port is being used.
If the value is set to 1, the backup port is being utilized.
4014 Bad
CKS This word contains the total number of frames received by the
module that contain a bad check-sum values in the message.
4015 Sync
Errors
This word contains the total number of frames received by the
module that have synchronization errors. Each frame in the
protocol has a specific header that must be received in a fixed
sequence. If this header is not received correctly, this word will
be incremented, and the frame will be discarded.
4016 Length
Errors
This word contains the total number of frames received by the
module that do not have the correct length.
4017 Timeout This word contains the total number of frames received by the
module that were not received within the specified receive
timeout parameter.
4018 RX
Frames
This word contains the total number of frames received by the
module.
4019 TX
Frames
This word contains the total number of frames transmitted by
the module.
4020
MSP Event Buffer This parameter shows the number of events available in the
event buffer for M_SP_NA points.
4021
MDP Event Buffer This parameter shows the number of events available in the
event buffer for M_DP_NA points
4022
MST Event Buffer This parameter shows the number of events available in the
event buffer for M_ST_NA points
4023
MMENA Event
Buffer
This parameter shows the number of events available in the
event buffer for M_ME_NA points
4024
MMENB Event
Buffer
This parameter shows the number of events available in the
event buffer for M_ME_NB points