ProSoft Technology MVI56-101S User Manual
Page 136

Reference MVI56-101S
♦ ControlLogix Platform
User Manual
IEC 60870-5-101 Slave Communication Module
Page 136 of 193
ProSoft Technology, Inc.
August 2, 2011
C_BO_NA
A Control 32-Bit Bitstring Command information object occupies two words and
uses double-word addressing.
For example, if you configured the following information objects:
These information objects would be used as follows:
Inf. Object Address
Module Database Address
3100
Words 3000 and 3001 (Double-word address 1500)
600
Words 2000 and 2001(Double-word address 1000. Must
match the configuration of point 600 in M_BO_NA.)
3101
Words 3002 and 3003 (Double-word address 1501)
601
Words 2002 and 2001 (Double-word address 1001. Must
match the configuration of point 601 in M_BO_NA.)
3102
Words 3003 and 3004 (Double-word address 1502)
602
Words 2004 and 2005 (Double-word address 1002. Must
match the configuration of point 602 in M_BO_NA.)