And if the parameter offsets are configured as follows:
It would imply that the parameter points would be configured as follows:
M_ME_NA
Monitored Measured Normalized Point
Associated Parameter Point
400 2400
401 2401
402 2402
403 2403
404 2404
So, in order to send change the deadband for the M_ME_NA point 400, the
Master would send a command type 110 to point 2400: