ProSoft Technology MVI56-101S User Manual
Page 146

Reference MVI56-101S
♦ ControlLogix Platform
User Manual
IEC 60870-5-101 Slave Communication Module
Page 146 of 193
ProSoft Technology, Inc.
August 2, 2011
Data Type Level
You can configure whether a data type should generate events. Each data type
has a configuration parameter to control the generation of events:
In the example above, only the M_SP_NA points would generate events.
Point Level
You can configure whether each point should generate events using the Group
field for each point configuration. To disable event generation for a specific port,
set the value to 40000000.