2.6 [M_DP_NA_1]
This section defines the monitored dual-point database. This information is
sourced from the database and is transferred to the remote Master unit.
This section takes the following parameters:
P
OINT
#
DB
ADDRESS
G
ROUPS
IV
DB
B
IT
Each point consumes two bits (00 = intermediate, 01 = off, 10 = on and 11 =
intermediate). The DB
A
DDRESS
value corresponds to the bit offset address in
the database.
The DB
ADDRESS
should be located in a database area that is being constantly
moved from the module to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.