Configuring the MVI56-101S Module
MVI56-101S ♦ ControlLogix Platform
User Manual
IEC 60870-5-101 Slave Communication Module
Page 66 of 193
ProSoft Technology, Inc.
August 2, 2011
2.17 [C_SE_NA_1]
This section defines the normalized setpoint database. This information is
sourced from the remote Master and is transferred to the database.
You can associate a command with a monitored single-point database value to
coordinate the command/monitor operation. You must enter the correct M
ONITOR
P
OINT
# and M
ONITOR
DB
ADDRESS
values in the table. If the R
EQUIRE
S
ELECT
parameter is not set to zero, a select command must be received before an
execute command will be processed.
This section takes the following parameters:
P
OINT
#
DB
ADDRESS
M
ONITOR
P
OINT
#
M
ONITOR
DB
ADDRESS
R
EQUIRE
S
ELECT
Each point consumes one word. The DB
A
DDRESS
value corresponds to the word
offset in the database.
The
DB
ADDRESS
should be located in a database area that is being constantly
moved from the Master to the module.
For additional information on how to set these parameters, see the Reference
chapter of this manual.