ProSoft Technology MVI56-101S User Manual
Page 52

Configuring the MVI56-101S Module
MVI56-101S ♦ ControlLogix Platform
User Manual
IEC 60870-5-101 Slave Communication Module
Page 52 of 193
ProSoft Technology, Inc.
August 2, 2011
2.4.3 Point
Count
Point Count configuration ranges in the following configuration items are based
on the assumption that you will be using only one of the available data types for
your application. The number of point counts you configure will have an effect on
module performance, in particular, the accuracy of the module’s internal clock.
Parameter Description
Range
M_SP_NA point count
The number of point values assigned in monitored
single-point database.
0 to 1000
M_DP_NA point count
The number of point values assigned in monitored
double-point database.
0 to 1000
M_ST_NA point count
The number of point values assigned in monitored
step-point database.
0 to 1000
M_BO_NA point count
The number of 32-bit values assigned in monitored
bitstring database
0 to 1000
M_ME_NA point count
The number of point values assigned in monitored
normalized-point database.
0 to 1000
M_ME_NB point count
The number of point values assigned in monitored
scaled-point database.
0 to 1000
M_ME_NC point count
The number of point values assigned in monitored
scaled short-float point database.
0 to 50
M_IT_NA point count
The number of point values assigned in monitored
counter-point database.
0 to 99
C_SC_NA point count
The number of point values assigned in command
single-point database.
0 to 1000
C_DC_NA point count
The number of point values assigned in command
dual-point database.
0 to 1000
C_RC_NA point count
The number of point values assigned in command
step-point database.
0 to 1000
C_BO_NA point count
The number of 32-bit values assigned in command
bitstring database
0 to 1000
C_SE_NA point count
The number of point values assigned in command
normalized-point database.
0 to 1000
C_SE_NB point count
The number of point values assigned in command
scaled-point database.
0 to 1000
C_SE_NC point count
The number of point values assigned in command
short-float point database.
0 to 50