ProSoft Technology MVI56-101S User Manual
Page 151
![background image](https://www.manualsdir.com/files/866109/content/doc151.png)
MVI56-101S ♦ ControlLogix Platform
Reference
IEC 60870-5-101 Slave Communication Module
User Manual
ProSoft Technology, Inc.
Page 151 of 193
August 2, 2011
5.3.7 Invalid
Bit
Monitoring
This feature allows the application to set the invalid (IV) quality bit of data points
for all supported Monitored ASDU types. If the feature is enabled, the status of
each point configured by the user can have the individual IV quality bit
determined by the processor.
The parameters required to support this feature are:
Cyclic Set IV Time
IV Check Delay Time
IV Fail Count
To disable this feature, set the IV Fail Count parameter to 0. If the IV bit field is
absent or set to 0, the invalid quality state for the point will always be reported as
valid. If used, the Cyclic Set IV Time parameter must be at least 3 times larger
than the IV Check Delay Time.
The C
YCLIC
S
ET
IV
T
IME
parameter determines the interval at which the driver will
set all the IV bits for the points being monitored in the module. If the IV bit is ON
for the number of times specified by the IV
F
AIL
C
OUNT
parameter , the point is in
an invalid state. The driver will check the state of each bit at the frequency
determined by the IV
C
HECK
D
ELAY
T
IME
.
The values for the parameters must permit the driver to properly execute the
logic. For example, the value for C
YCLIC
S
ET
IV
T
IME
should be twice the IV
C
HECK
D
ELAY
T
IME
,
multiplied by the IV
F
AIL
C
OUNT
. If the cyclic timer is set to a
smaller value, the logic may not execute correctly.