74
Table 41
Liebert XDH specifications
Models
XDH20DKP-0
XDH20DK--0
XDH20BKP-0
XDH20BK--0
XDH20DKPE0
XDH20DK-E0
XDH20BKPE0
XDH20BK-E0
(60Hz)
XDH32DKP-0
XDH32DK--0
XDH32BKP-0
XDH32BK--0
XDH32DKPE0
XDH32DK-E0
XDH32BKPE0
XDH32BK-E0
(60Hz)
XDH20DSP-0
XDH20DS--0
XDH20BSP-0
XDH20BS--0
XDH20DSPE0
XDH20DS-E0
XDH20BSPE0
XDH20BS-E0
(50/60Hz)
XDH32DSP-0
XDH32DS--0
XDH32BSP-0
XDH32BS--0
XDH32DSPE0
XDH32DS-E0
XDH32BSPE0
XDH32BS-E0
(50/60Hz)
Cooling Capacity
XDH20, 60Hz Nominal (98ºF [37°C] EAT): 22kW/6.3 Tons
XDH20, 60Hz Maximum(105ºF [40°C] EAT): 25.5kW/7.3 Tons
XDH20, 50Hz Nominal (98ºF [37°C] EAT): 19kW / 5.4 Tons
XDH20, 50Hz Maximum(116ºF [47°C] EAT): 25.5kW/7.3 Tons
XDH32, 60Hz Nominal (98ºF [37°C] EAT): 30kW/8.5 Tons
XDH32, 60Hz Maximum(105ºF [40°C] EAT): 34.5kW/7.3 Tons
XDH32, 50Hz Nominal (98ºF [37°C] EAT): 27kW / 7.7 Tons
XDH32, 50Hz Maximum(108ºF [42°C] EAT): 34.5kW/7.3 Tons
Conditions
Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew
point
Electrical Requirements
Input
120V-1ph-60Hz
220-240V-1ph-50Hz, CE /
208-240V-1ph-60Hz, CSA
Input Power Connections
Two IEC320-C14 power inlets and two IEC
power cords with NEMA 5-15P connectors
Two IEC320-C14 power inlets and two IEC
power cords with IEC320-C14 receptacles
Full Load Amps
5
10
2.5
5
Power Consumption,
Nominal, Watts
600
1200
575
1150
Dimensions, inches (mm)
Height—Unit Only
78 (1981)
Height—Including
Pipe Connections
80 (2032)
Width
12 (305)
Depth
42 (1067)
Weight, lb (kg)
Unit Only
233 (106)
246 (112)
233 (106)
246 (112)
Shipping Weight
317 (144)
330 (150)
317 (144)
330 (150)
Number of Fans
6
Airflow, Nominal,
ft
3
/min (m
3
/hr)
2500 (4248)
4000 (6796)
2428 (4125)
3850 (6541)
Audible Noise,
Sound Power
81 dBa
86 dBa
81 dBa
86 dBa
Pipe Connections
Refrigerant Supply
1/2" OD, Cu (optional 1/2" threaded one-shot coupling on the unit)
Refrigerant Return
7/8" OD, Cu (optional 7/8" threaded one-shot coupling on the unit)
Serviceable Parts
Fans and electrical components
Cabinet Exterior Finish
Black, matte finish, heat-fused powder coat
Options
Condensate Sensing (factory-installed)
Dry contact outgoing signal (24VAC - 1A maximum)
One-shot style flex pipe connections
Uni-directional or bi-directional air diffusers
Agency
Approvals
CSA 60Hz
CE 50Hz, CSA 50/60Hz