3 liebert xdcf standard features, Figure 39 liebert xdcf hydraulic diagram, Liebert xdcf standard features – Emerson Liebert Xtreme Density User Manual
Page 46
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
40
4.3
Liebert XDCF Standard Features
The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and
equipment without exhausting heat into the room.
Upper and lower modules may be mounted on the rear of an Egenera BladeFrame. Liebert XDCF
modules use R-134a refrigerant. When attached to a fully loaded BladeFrame EX rack, each Liebert
XDCF module has a nominal cooling capacity of 10kW (2.8 tons; 34,000 BTUh). Performance is based
on:
• Entering fluid temperature—55°F (12.8°C) and
• Dew point—50°F (10°C) or lower.
Liebert XDCF modules consist of a sheet-metal frame, coil and filter dryer. It has no moving parts
and needs no electricity.
The Liebert XDCF system (see Figure 39 below) consists of:
• Liebert XDCF modules—upper and lower models are available
• Flex pipe—connects Liebert XDCF units to supply and return piping
• Liebert XD Piping—delivers pumped R-134a refrigerant through flexible piping
• Liebert XDP or Liebert XDC—supplies R-134a refrigerant to Liebert XDCF modules
(see Liebert XDP or Liebert XDC user manual for required chiller or drycooler)
Figure 39 Liebert XDCF hydraulic diagram
Liebert
XDC
or
Liebert XDP
XD
Cooling
Module *
XD
Cooling
Module *
XD
Cooling
Module *
XD
Cooling
Module *
Pumped
Refrigerant
Liebert
XDC
or
Liebert XDP
Supply Lines
(2 per unit)
Return Lines
(2 per unit)
Pumped
Refrigerant
* XD CoolFrame,
XDH, XDO or XDV