beautypg.com

Table 33 liebert xdo20 specifications, Table 33, Liebert xdo20 specifications – Emerson Liebert Xtreme Density User Manual

Page 75

background image

Specifications

69

Table 33

Liebert XDO20 specifications

Models

XDO20DK--*; XDO20BKP-*

XDO20DKP-*; XDO20BK-E*

XDO20DK-E*; XDO20BKPE*

XDO20DKPE*

XDO20BS--*; XDO20DS--*

XDO20BSP-*; XDO20DSP-v

XDO20BS-E*; XDO20DS-E*

XDO20BSPE*; XDO20DSPE*

60Hz

60Hz

50Hz

Cooling Capacity

Nominal (92°F [33°C] EAT): 20kW / 5.7 Tons

Maximum (100°F [38°C] EAT): 23kW / 6.5 Tons

Nominal (92°F [33°C] EAT):

17.7kW / 5 Tons

Maximum (103°F [39°C]

EAT): 23kW / 6.5 Tons

Conditions

Capacity rating is @ 55ºF (13°C) Entering Fluid Temperature and

50ºF (10°C) or lower dew point

Electrical Requirements

Input Voltage

1ph-60Hz-120V

1ph-60Hz-220-240V

1ph-50 Hz-220-240V

Input Power Connections

Terminal blocks provided internal to unit

Full Load Amps

2.7A @ 120V

1.64A @ 230V

1.47 @ 230V

Wire Size Amps

3.4

2.0

1.84

Overcurrent Protection Device

15

15

15

Power consumption,

nominal, watts

335

350

250

Dimensions, inches (mm)

Length

72-1/4 (1835)

Width

24-1/8 (613)

Height

22-1/2 (572) not including electrical and piping access

Weight, lb (kg)

Unit only

150 (68)

Shipping weight

238 (108)

296 (134)

Installed, with refrigerant,

without options

155 (70)

Number of Fans

1

1

Airflow, Nominal, ft

3

/ min

(m

3

/ hr)

2700 (4587)

2250 (3822)

Audible Noise

85 dBa sound power

83 dBa sound power

Pipe Connections (without flex pipe)

Refrigerant Supply

from Liebert XDP/Liebert XDC

1/2" OD, Copper

Refrigerant Return

to Liebert XDP/Liebert XDC

7/8" OD, Copper

Serviceable Parts

Fan and electrical components

Exterior Finish – Bottom,

Sides, Front and Rear

Black matte finish, heat-fused powder coat

Exterior Finish - Top

Hot-dipped galvanized steel

Agency

Approvals

CSA 60 Hz

CE 50Hz

Options

Lighting Fixtures (ship loose) 2 Liebert XDOs per lighting unit; 120V or 277V; 4’ standard fluorescent tubes (not included)

Power, optional lighting fixture

0.9A per 120V light fixture;

0.4A per 277V light fixture

None

Condensate sensing

(factory-installed)

Dry contact 24VAC - 1A maximum

Pre-Charged Refrigerant

R-134a Refrigerant, one-shot connections

* = Revision level