28

3.16.2 Calculating Refrigerant Charge—Example

Using Tables 7, 8, 9 and 10, calculate the refrigerant charge of the individual sections of your Liebert

XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant

required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF,

Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDP with 20

Liebert XDV8 cooling modules.

Verify that the refrigerant volume of the Liebert XD system with the longest piping length is within

the allowable limit. If the allowable limit is exceeded, the Liebert XDP/Liebert XDC should be moved

closer to the cooling modules (refer to 3.12 - Liebert XD Refrigerant for limits and related details).

Another way to shorten the total pipe length is to reroute the pipe runs.

3.17 Liebert XDC DX R-407c Circuit Volume—Air Cooled Units

Weigh in the calculated charge based on Tables 13, 14 and 15.

Table 11

Calculating refrigerant charge—example

Components

Number of Units

or Piping Length, feet

Pounds Per Component

Total, lb.

Liebert XDP/Liebert XDC

1

157

157

Liebert XDV8 Cooling Modules

20

2.32

46.4

Supply Main, 1-1/8"

100

0.45

45

Return Main, 2-1/8"

100

0.28

28

Liebert XDV 1/2" supply Flex

Pipes

20

0.8

16

Liebert XDV 5/8" return Flex

Pipes

20

0.03

0.6

Total

293

Table 12

Worksheet to calculate refrigerant charge

Components

Number of Units

or Piping Length

Pounds Per Component

Total

Total

!

CAUTION

Risk of improper lubrication. May cause equipment damage.
Liebert XDCs with refrigerant R-407c charges over 35 lb. (15.9kg) require additional oil. Refer

to the Liebert XDC user manual, SL-16671, available at Liebert’s Web site,

www.liebert.com

Table 13

Indoor unit refrigerant charge—R-407c

Model 60/50 Hz

Charge/Circuit, lb. (kg)

Liebert XDC160

17.5 (8.0)