Specifications

68

Table 32

Liebert XDO16 specifications

Models

XDO16BK--0

XDO16DK--0

XDO16BK-E0

XDO16DK-E0

XDO16BKP-0

XDO16BKPE0

XDO16DKP-0

XDO16DKPE0

(60Hz)

XDO16BSP-0

XDO16BSPE0

XDO16DSP-0

XDO16DSPE0

XDO16BS--0

XDO16DS--0

XDO16BS-E0

XDO16DS-E0

(60Hz)

XDO16BSP-0

XDO16BSPE0

XDO16DSP-0

XDO16DSPE0

XDO16BS--0

XDO16DS--0

XDO16BS-E0

XDO16DS-E0

(50Hz)

Cooling Capacity

Nominal (92°F [33°C] EAT): 17.2kW / 5 Tons

Maximum (90°F [32°C] EAT): 17.2 kW / 5 Tons

Nominal (92°F [33°C]

EAT): 17.1kW/4.9Tons

Maximum (93°F [34°C]

EAT): 17.2 kW / 5 Tons

Conditions

Capacity rating is @ 55°F (13°C) Entering Fluid Temperature and 50ºF or lower dew point

Electrical Requirements

Input Voltage

1ph-60Hz-120V

1ph-50 Hz-220-240V

1ph-50 Hz-230V

Input Power Connections

Terminal blocks provided internal to unit

Full Load Amps

2.7A @ 120V

1.50 @ 230V

1.19 @ 230V

Wire Size Amps

3.4

2.0

1.28

Overcurrent Protection Device

15

15

15

Power consumption,

nominal, watts

335

250

250

Dimensions, inches (mm)

Length

72-1/4 (1835)

Width

24-1/8 (613)

Height

22-1/2 (572) not including electrical and piping access

Weight, lb (kg)

Unit only

150 (68)

Shipping weight

238 (108)

296 (134)

Installed, with refrigerant,

without options

155 (70)

Number of Fans

1

1

Airflow, Nominal, ft

3

/ min

(m

3

/ hr)

2700 (4587)

2250 (3822)

Audible Noise

85 dBa sound power

83 dBa sound power

Pipe Connections

Refrigerant Supply

from Liebert XDP/Liebert XDC

1/2" OD, Copper

Refrigerant Return

to Liebert XDP/Liebert XDC

7/8" OD, Copper

Serviceable Parts

Fan and electrical components

Exterior Finish – Bottom,

Sides, Front and Rear

Black, matte finish, heat-fused powder coat

Exterior Finish - Top

Hot-dipped galvanized steel

Agency

Approvals

CSA 60 Hz

CSA 60Hz

CE 50Hz

Options

Lighting Fixtures (ship loose)

2 Liebert XDOs per lighting unit; 120V or 277V; 4’ standard fluorescent tubes (not included)

Power, optional lighting fixture

0.9A per 120V light fixture; 0.4A per 277V light fixture

None

Condensate sensing

(factory-installed)

Dry contact 24VAC - 1A maximum