1 liebert xdo standard features, 1 optional features liebert xdo, Iebert – Emerson Liebert Xtreme Density User Manual

Page 36: Xd c, Ooling, Odules, Xdo, l, Xdv, l, Xdcf, Liebert xdo standard features

background image

Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

30

4.0

L

IEBERT

XD C

OOLING

M

ODULES

—L

IEBERT

XDO, L

IEBERT

XDV, L

IEBERT

XDH

AND

L

IEBERT

XDCF

4.1

Liebert XDO Standard Features

• Micro Channel Heat Exchanger—The Liebert XDO unit includes two all-aluminum micro channel

heat exchangers.

• Fan—Air is drawn in the sides of the unit through the heat exchangers and is discharged by the

fan to the area below—Liebert XDO fan tray hinges down to allow access to replace or service all

electrical components.

• Internal Mounting—The Liebert XDO unit is typically suspended from the overhead building

structure by inserting field-supplied threaded rods into the internal mounting brackets.

4.1.1 Optional Features Liebert XDO

Refrigerant Pre-Charge—Liebert XDO units with the pre-charged refrigerant option will have

one-shot style fittings or removable couplings that contain pressurized refrigerant inside the Lie-

bert XDO. The fittings ease connection to Liebert XD Piping and filling with refrigerant.

Field-Installed Flexible Piping (for use with prefabricated piping assemblies)—Field-installed

flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters). Con-

nection style to the unit end may be straight or 90 degrees. Connection to the prefabricated piping

assembly is with a threaded coupler. For information on acquiring the correct kit for your instal-

lation, refer to DPN000780, available by calling 1-800-LIEBERT and from your local Emerson

Network Power representative.

External Mounting Brackets—The Liebert XDO unit can be suspended by external mounting

brackets that are attached to the front and rear panels of the unit. The external mounting brack-

ets are optional ship-loose items.

Condensate Detection—The Liebert XDO unit is available with optional factory-installed con-

densate detection. The condensate detection has connection points (dry contacts) inside the unit.

Lighting Fixture—Field-installable lighting fixtures are available in two voltages, 120V and

277V. Light Fixture maybe attached to the bottom of the light panel to the left and right of the

fan. Each fixture consists of housing, reflector, ballast and diffuser. Fixtures are compatible with

standard 48" fluorescent tubes. Lamps are not included.