8 liebert xdp—pumping unit, 1 liebert xdp minimum load, Figure 10 liebert xdp pumping unit – Emerson Liebert Xtreme Density User Manual
Page 14: Liebert xdp—pumping unit, Liebert xdp minimum load, 1 - liebert xdp mini, Mum load
System Description
8
1.8
Liebert XDP—Pumping Unit
The Liebert XDP isolates the building’s chilled water circuit from the pumped refrigerant circuit. The
Liebert XDP circulates refrigerant to Liebert XDCF, Liebert XDH, Liebert XDO or Liebert XDV mod-
ules while preventing condensation by maintaining the refrigerant’s temperature above the dew
point. The Liebert XDP employs two sets (for redundancy) of remote sensors to determine the temper-
ature and humidity in the air and instantly adjusts refrigerant supply temperature to compensate for
changing conditions.
1.8.1
Liebert XDP
Minimum Load
The Liebert XDP’s minimum recommended operating load is 20% of system nominal capacity. For
example, a Liebert XDP160 60Hz system’s minimum load would be 32 kW. Loading below this value
can unfavorably affect system operation. Consult factory for any loading below this recommendation.
Figure 10 Liebert XDP pumping unit