Figure 57 liebert xdc piping locations, Table 25, Liebert xd chiller piping connection sizes – Emerson Liebert Xtreme Density User Manual

Page 62

background image

Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

56

Figure 57 Liebert XDC piping locations

Table 25

Liebert XD Chiller piping connection sizes

Air Cooled Models

Piping Outlet Connection Sizes, OD Cu, inches

50/60Hz

A

B

C

D

E

F

G

Liebert XDC160

1-3/8

7/8

-

-

-

2-1/8

1-1/8

Install replaceable filter dryer
assembly in liquid supply line G

** To first cooling module
or bypass flow controller

Dimensions are
approximate and
subject to change
without notice.

G - Supply to Cooling Units

F - Return From Cooling Units

B - Liquid
Refrigerant Lines

* Allow 8" (204mm) of clearance for filter replacement

** To ensure all refrigerant flow is filtered, install the filter dryer assembly

between the discharge line of the XDC and the first bypass flow controller
or the first cooling module.

A - Hot Gas
Refrigerant Lines

* Orientation determined
by installer.

23"

(584.2mm)

6" (152mm)

47"

(1193.8mm) 44"

(1117.6mm)

DPN000768
Page 3, Rev. 6