Table 20 five-port prefabricated piping legend, Table 20, Five-port prefabricated piping legend – Emerson Liebert Xtreme Density User Manual
Page 55
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
49
Figure 48 Five-port prefabricated piping for Liebert XD cooling modules
Table 20
Five-port prefabricated piping legend
Branch Piping
Standard Run
Long Run *
Five Port
185797G51
185800G51
Supply
inch (mm)
Outside Diameter (ODS)
1-1/8
1-3/8
Height (H)
8-3/4 (222)
8-1/2 (216)
Length (L)
6-3/4 (171)
7 (178)
Return
inch (mm)
Outside Diameter (ODR)
2-1/8
2-5/8
Height (H)
10-1/2 (267)
10-1/2 (267)
Length (L)
8-3/4 (222)
9-1/8 (232)
* Pipe runs greater than 60 equivalent feet
DPN000773
Page 3, Rev. 3
Return
Supply
120"
(3048mm)
24"
(610mm)
Ref. Typ.
8-5/16"
(211mm) Ref. Typ.
4-5/8"
(117mm)
Nominal
ODR
ODS
H
L