beautypg.com

Table 20 five-port prefabricated piping legend, Table 20, Five-port prefabricated piping legend – Emerson Liebert Xtreme Density User Manual

Page 55

background image

Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

49

Figure 48 Five-port prefabricated piping for Liebert XD cooling modules

Table 20

Five-port prefabricated piping legend

Branch Piping

Standard Run

Long Run *

Five Port

185797G51

185800G51

Supply

inch (mm)

Outside Diameter (ODS)

1-1/8

1-3/8

Height (H)

8-3/4 (222)

8-1/2 (216)

Length (L)

6-3/4 (171)

7 (178)

Return

inch (mm)

Outside Diameter (ODR)

2-1/8

2-5/8

Height (H)

10-1/2 (267)

10-1/2 (267)

Length (L)

8-3/4 (222)

9-1/8 (232)

* Pipe runs greater than 60 equivalent feet

DPN000773
Page 3, Rev. 3

Return

Supply

120"

(3048mm)

24"

(610mm)
Ref. Typ.

8-5/16"

(211mm) Ref. Typ.

4-5/8"

(117mm)

Nominal

ODR

ODS

H

L