beautypg.com

Section 3 - operation, 1 general, 2 local mode operation – KEPCO KLR Series User Manual User Manual

Page 41: 1 turning the power supply on, General -1, Local mode operation -1, Turning the power supply on -1

background image

KLR091313

3-1

SECTION 3 - OPERATION

3.1

GENERAL

This section explains how to operate the KLR Power Supply. Series KLR feature three modes of
operation:

• Local Mode (see PAR. 3.2): This is the default operating mode, providing full access to

all programming and readback functions via front panel displays, controls, and indica-
tors.

• Digital Remote Mode (see PAR. 3.3): This mode is selected via commands transmitted

through one of the two digital ports. One port is configured for IEEE-488 (GPIB), The
second port is either an RS 232 port [standard models] or a LAN port [E-Series models].
The digital ports are described in the KLR Developer’s Guide. The power supply auto-
matically goes into digital remote mode when commands are accepted via one of the
digital ports.

• Analog Remote Mode (see PAR. 3.4): This mode is selected via a jumper wire at the

analog programming port prior to initial turn-on, and provides limited access to program-
ming and readback functions.

3.2

LOCAL MODE OPERATION

Local operation of the KLR Power Supply is accomplished via the front panel switches and con-
trols illustrated in Figure 2-1 and described in detail in Table 2-1. Separate 4-digit LEDs display
actual output voltage and current; these same displays show set points and limits as well. Status
and fault indications are provided by a 4-character alpha-numeric display.

3.2.1

TURNING THE POWER SUPPLY ON

1. To turn the power supply on, set POWER ON/OFF circuit breaker (see Figure 2-1) to ON.

Apply firm, continuous pressure to rocker actuator until fully engaged (right side of rocker
actuator locked parallel to front panel). If actuator does not lock when released, allow actua-
tor to return to starting position, then wait a few seconds before repeating turn-on sequence.

CAUTION: DO NOT attempt to “tease” the switch contacts closed by repetitive press-

and-release action. The circuit breaker is “trip-free” design; if overload
exists, contacts cannot be held closed by actuator. After turning the unit off,
allow at least 5 seconds before turning the unit on again.

2. When the power supply is turned on, it performs a self-test and displays the following infor-

mation:

• Status display flashes KLR for 2 seconds while DC VOLTS and DC AMPERES dis-

plays show the maximum voltage and current capability of the unit.

• Status display flashes LAN for 2 seconds if unit is an E-Series model

• Status display flashes RODC for 2 seconds if unit has the Rapid Output Discharge Cir-

cuit option installed.

• Status display flashes LMT for 2 seconds while DC VOLTS and DC AMPERES dis-

plays show the maximum voltage and current allowed for a previously programmed
Limit model. To reprogram the maximum allowable voltage and/or current, refer to
PAR. 3.2.9 to define a Limit model.