beautypg.com

RISCO Group axesplus® User Manual

Page 23

background image

User Manual for Hardware Installation

Uncontrolled when printed

© RISCO Group

22

ACIB to AC/DC Converter

1. Connect the PWR SYS 0V and PWR RLY 0V of ACIB to the negative ground of AC/DC

Converter.

2. Connect the positive power of the Converter to PWR SYS 12V and PWR RLY 12V of ACIB.

5.4

Installation/Programming Mode for ACCB

In case ACCB is not able to communicate with a Proxy, you can still ensure that the access control

system is functional using this mode. When the ACCB has no configurations and is not able to

communicate with the proxy, using this mode we can make the access control system functional.

When the ACCB is booted up, the readers connected with the ACIB start blinking (alternate red and

green). This indicates that the ACCB is in programming mode.

To provide access to a person (to a card) you need to configure a master card for that ACCB. You can

have only one master card for a single ACCB. Any first card swiped thrice on the reader (connected

to the ACCB) becomes the Master Card.

Perform the following steps to create a master card:

1. Swipe a card on the reader.
2. Swipe the same card two more times irrespective of the reader on which you swiped for

the first time. The master card is created. The readers stop blinking once the master card is
created.

You need to swipe the card to which you want to provide access on the reader. The card details are

added to the ACCB database and henceforth this card will be granted access every time it is swiped.

The following section describes the steps to add the card to the ACCB database.