RISCO Group axesplus® User Manual
Page 21

User Manual for Hardware Installation
Uncontrolled when printed
© RISCO Group
20
ACCB to PMC Connection
RAN BUS 1 of the ACCB is connected to the RAN BUS of the PMC.
3. Connect GRN from RAN BUS1 on ACCB to the GRN of RAN BUS on PMC.
4. Connect YEL wire of RAN BUS1on ACCB to the YEL of RAN BUS on PMC.
5. Connect the COM BLK on RAN BUS1 from ACCB to the black negative ground (COM2 BLK)
from AUX2 on PMC.
6. Connect PWR2 RED from PMC to AUX RED of RAN BUS 1 on ACCB.
ACIB to PMC Connection
Connect the System Power (PWR SYS 0V) of ACIB to COM1 BLK of AUX 1 on PMC
1. Connect PWR1 RED of AUX1 on PMC to System Power 12V (PWR SYS 12V) of ACIB
2. Connect Relay Power 0V (PWR RLY 0V) of ACIB to COM2 BLK of AUX 2 on PMC
3. Connect PWR2 RED of AUX2 on PMC to PWR RLY 12V as shown in the above figure.
Other Connections
1. Connect the positive of the battery (BAT.) of PMC to the positive of the external Battery.
2. Connect the negative of the battery (BAT.) of PMC to the negative of the external Battery,
ratings 12 V and 7 Ah.
3. Connect the AC/DC converter to the Power Input of PMC as shown in the figure above.