Specifications, General – Precision Digital PD6310 User Manual
Page 9

Model PD6210 & PD6310 Batch Controllers
Instruction Manual
9
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY
Upper display: 0.6" (15 mm) high, red LEDs
Lower display: 0.46" (12 mm) high, red LEDs
6 digits: each (-99999 to 999999), with lead zero blanking.
DEFAULT
DISPLAY
ASSIGNMENT
The Upper display shows batch total. The Lower display
shows rate with alternating units, and can be switched to
show grand total, batch count, or preset with the STOP key.
CUSTOM
DISPLAY
ASSIGNMENT
The Upper and Lower displays may be assigned to rate,
total, grand total, batch count, preset, set points, units
(lower display only), alternating R & T, R & GT, preset &
rate, max & min, or a Modbus display register. Any
rate/total/grand total display may be programmed to
alternate with a custom unit or tag.
ALTERNATING
DISPLAY
Displays alternate every 10 seconds when display is
selected or the batch is paused.
DISPLAY
INTENSITY
Eight user selectable intensity levels
DISPLAY
UPDATE RATE
5/second (200 ms)
OVERRANGE
Display flashes
999999
UNDERRANGE
Display flashes
-99999
FRONT PANEL
NEMA 4X, IP65
PROGRAMMING
METHODS
Four front panel buttons, digital inputs, PC and MeterView
Pro software, or cloning using Copy function.
NOISE FILTER
Programmable from 2 to 199 (0 will disable filter)
(PD6210 only)
FILTER BYPASS
Programmable from 0.1 to 99.9% of calibrated span
(PD6210 only)
RECALIBRATION
All ranges are calibrated at the factory. Recalibration is
recommended at least every 12 months.
MAX/MIN
DISPLAY
Max/min readings reached by the process are stored until
reset by the user or until power to the controller is cycled.