Pd6210 process input – Precision Digital PD6310 User Manual
Page 11

Model PD6210 & PD6310 Batch Controllers
Instruction Manual
11
ENCLOSURE
1/8 DIN, high impact plastic, UL 94V-0, color: black
MOUNTING
1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies are provided.
TIGHTENING
TORQUE
Screw terminal connectors: 5 lb-in (0.56 Nm)
OVERALL
DIMENSIONS
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm)
(W x H x D)
WEIGHT
9.5 oz (269 g)
WARRANTY
3 years parts & labor
PD6210 Process Input
INPUTS
Field selectable:
0-20, 4-20 mA,
±10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)
ACCURACY
±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy range:
10-100% of calibrated span
TEMPERATURE
DRIFT
0.005% of calibrated span/
°C max from 0 to 65°C ambient,
0.01% of calibrated span/
°C max from -40 to 0°C ambient
SIGNAL INPUT
CONDITIONING
Linear, square root, or programmable exponent
MULTI-POINT
LINEARIZATION
2 to 32 points
PROGRAMMABL
E EXPONENT
1.0001 to 2.9999
LOW-FLOW
CUTOFF
0-999999 (0 disables cutoff function)
DECIMAL POINT
Up to five decimal places or none:
d.ddddd
, d.dddd, d.ddd, d.dd, d.d,
or
dddddd
CALIBRATION
RANGE
Input
Range
Minimum Span
Input 1 & Input 2
4-20 mA 0.15 mA
±10 V
0.10 V
An error message will appear if the input 1 and input 2
signals are too close together.
INPUT
IMPEDANCE
Voltage ranges: greater than 500 k
Ω
Current ranges: 50 - 100
Ω
(depending on resettable fuse impedance)
INPUT
OVERLOAD
Current input protected by resettable fuse, 30 VDC max.
Fuse resets automatically after fault is removed.
F4 DIGITAL INPUT
CONTACTS
3.3 VDC on contact. Connect normally open contacts
across F4 to COM.