Model PD6210 & PD6310 Batch Controllers
Instruction Manual
84
Minimum Input Span
The minimum input span is the minimum difference between input 1 and 2
signals required to complete the calibration or scaling of the controller.
Input range
Input 1 & input 2 span
4-20 mA
0.15 mA
±10 VDC
0.10 VDC
Controller Copy Function (Copy)
The Copy function is used to copy (or clone) all the settings from one
controller to other controllers requiring exactly the same setup and
programming (i.e. type of input, scaling, decimal point, filter, bypass,
etc.).
Warning!
Only the PDA1200 meter copy cable must be used for
meter-to-meter interfacing. Using standard CAT5 or
other cable will cause damage to both controllers.
Copy Function Requirements
To successfully copy settings from one controller to another, both
controllers must have the same software version and baud rate setting.
See Determining Software Version, page 85 for instructions.
Controller Copy or Cloning Instructions
!
Caution!
Do not connect the two controllers to the same signal
source while cloning. Internal calibration may be affected.
1. Connect two controllers using a PDA1200 controller copy cable.
2. Do not connect the two controllers to the same signal source.
3. Power up both controllers. Leave clone controller in Run Mode.
4. Enter
the
Advanced Features
menu of the Master controller see
ADVANCED OPERATION AND PROGRAMMING page 71.
5. Scroll
to
the
Copy
function using the Up arrow button then press
Enter.
6. The controller displays the message Send. Press Enter, the display
flashes while sending data. The message done is displayed when
copying is completed.