Model PD6210 & PD6310 Batch Controllers

Instruction Manual

84

Minimum Input Span

The minimum input span is the minimum difference between input 1 and 2
signals required to complete the calibration or scaling of the controller.

Input range

Input 1 & input 2 span

4-20 mA

0.15 mA

±10 VDC

0.10 VDC

Controller Copy Function (Copy)

The Copy function is used to copy (or clone) all the settings from one
controller to other controllers requiring exactly the same setup and
programming (i.e. type of input, scaling, decimal point, filter, bypass,
etc.).

Warning!

Only the PDA1200 meter copy cable must be used for
meter-to-meter interfacing. Using standard CAT5 or
other cable will cause damage to both controllers.

Copy Function Requirements

To successfully copy settings from one controller to another, both
controllers must have the same software version and baud rate setting.
See Determining Software Version, page 85 for instructions.

Controller Copy or Cloning Instructions

!

Caution!

Do not connect the two controllers to the same signal
source while cloning. Internal calibration may be affected.

1. Connect two controllers using a PDA1200 controller copy cable.
2. Do not connect the two controllers to the same signal source.
3. Power up both controllers. Leave clone controller in Run Mode.
4. Enter

the

Advanced Features

menu of the Master controller see

ADVANCED OPERATION AND PROGRAMMING page 71.

5. Scroll

to

the

Copy

function using the Up arrow button then press

Enter.

6. The controller displays the message Send. Press Enter, the display

flashes while sending data. The message done is displayed when
copying is completed.