Noise Filter (filter)
The noise filter is available for unusually noisy signals that cause an 
unstable process variable display. The noise filter averages the input 
signal over a certain period. The filter level determines the length of time 
over which the signal is averaged. The filter level can be set between 2 
and 199. The higher the filter level, the longer the averaging time and so 
the longer it takes the display to settle to its final value. Setting the filter 
level to zero disables the filter function. 
Note: The filter for a PD6310 works differently. There are two available 
settings: Hi Speed and Lo Speed (programmable from 2 to 50).
Noise Filter Bypass (bypass)
The noise filter bypass changes the behavior of the controller so that 
small variations in the signal are filtered out but large abrupt changes in 
the input signal are displayed immediately. The bypass value determines 
the minimum amount of signal change to be displayed immediately. All 
signal changes smaller than the bypass value are filtered or averaged by 
the controller. The noise filter bypass may be set between 0.1 and 99.9% 
of full scale. 
Rounding Feature (round)
The rounding feature is used to give the user a steadier display with 
fluctuating signals. Rounding is used in addition to the filter function. 
Rounding causes the display to round to the nearest value according to 
the rounding selected. This setting affects the last two digits, regardless 
of decimal point position. 
Modbus RTU Serial Communications (serial)
The controller is equipped with serial communications capability as a 
standard feature using Modbus RTU Serial Communication Protocol. 
To communicate with a computer or other data terminal equipment, an 
RS-232, RS-485, or USB adapter option is required; see Ordering 
Information
on page 7 for details.
Warning!
Do not connect any equipment other than Precision 
Digital’s expansion modules, cables, or controllers to 
the RJ45 M-LINK connector. Otherwise damage will 
occur to the equipment and the controller. 
Note: More detailed instructions are provided with each optional serial
communications adapter. Note: Refer to the
ProVu
®
Modbus
Register Tables located at www.predig.com for details.